| Inductive loop
vehicle detection is still the most reliable and
cost-effective method of vehicle detection in today's
traffic and parking applications. The electronic
circuitry in the Diablo Controls vehicle detectors is
very reliable, and its production and testing are
controlled very tightly. This assures the customer of
getting the most reliable electronic package available.
But this is only part of the story. The proper
installation of the loop system is something for which
the installer must take responsibility, and indeed, is
the key to reliable vehicle detection. It has been the
experience of most agencies and installers that a
properly installed loop system should last the life of
the roadbed. The loop "system" includes the loop wire in
the street and all of the feeder cable back to the
detector unit located at the gate operator or traffic
controller cabinet.
We would like to offer a few
tips and guidelines to follow for the proper
installation of vehicle detectors and street loops.
First, if there are old
loops present, remove all of the existing street loop(s).
An old loop in the pavement can act as a shorted turn
and can cause a low sensitivity situation.
The loop wire to
be installed in saw-cuts, should be #18 AWG or larger,
stranded and tinned copper wire. We recommend the use of
at least #16 wire for mechanical strength. Good wire is
typically inexpensive compared to the re-work expense if
a failure occurs. Cross-link polyethylene (XLPE)
insulation with a voltage rating of 600V is the wire to
use if a cold sealant is used. If a hot tar sealant is
used then a cross-link polyethylene with an additional
polyester jacket should be used, also with the 600 volt
rating. Cross-link polyethylene wire is recommended over
PVC insulated wire or nylon jacketed wire such as THHN
or TFFN.
The lead-in wire
should also be two conductor twisted, #16 AWG or larger
stranded wire . It is recommended that this wire also
have a high density polyethylene insulation.
The sawcut is one
one of the most important parts of the loop installation
process. The pavement is typically cut to a depth of
approximately 4 to 5 cm (1-1/2 to 2 inches) using a 6 mm
(1/4 inch) wide blade. The slot is then cleaned with
water and then blown out with compressed air. This will
assure that all sharp particles are removed from the
slot. The corners of all square or rectangular loops
should have 45 degree cuts to prevent sharp corners from
puncturing the loop wire. Start the 45 degree cuts about
8 to 12 inches from the corners of the loop. The turns
of wire are then installed in the bottom of the slot and
held into place with foam backer rod (See figure 2 ).
This will assure that the wire is held in place when the
sealant is added to the slot. Loop wires should be
twisted at least 6 turns per foot from the point where
they leave the loop and start toward the side of the
roadway - down the lead-in slot. The sealant used in the
loop and lead-in slot should be pliable and should
"give" with temperature changes in the pavement.

The roadway loop shown
above is a typical configuration for a street or roadway
installation. The loop shown is cut with a street saw
with straight slots. The corners are cut with 45 degree
cuts to prevent sharp corners. The two wires leave the
rectangular loop and are placed in another slot to exit
the roadway. The wires used in the main loop and the
exit slot must be one continuous piece. No splices can
be made in any part of the installation. The two wires
are twisted around each other at least 6 times per foot
and placed in the saw cut leaving the roadway.
Apply loop sealant
to this saw cut as well as the main loop. The wires are
then spliced to the lead-in cable at the concrete pull
box. All splices must be soldered!
Do Not Use wire nuts
or crimp type connectors! Tinned copper crimped
connections can be used to hold the wires together as
long as they are then soldered!
Most parking and
access control applications use unshielded, twisted
lead-in cable. Many times the lead-in cable used, is the
same loop wire twisted with a drill to maintain at least
the 6 turns per foot twist in the wire. Using lead-in
wire that is twisted is even more important if lead
in-wire from different loops are routed back to the
detectors in the same conduit.

The detail above shows a
cross section of the wire slot with 4 turns of wire
installed. Notice the backer rod holding the loop wires
in the slot. The sealant should completely fill the slot
up to the surface of the roadway. The top of the backer
rod should be at least 1 inch below the level of the
pavement.
The number of turns of
wire used in the loop is determined largely by the size
of the loop. Please refer to the table below for the
suggest number of turns. Increase the number of turns by
1 if the lead-in length exceeds 150 m (500 ft).
|
Loop Size |
Number of Turns |
|
0.6 x 1.2 m or
smaller |
2' x 4' or
smaller |
5 |
|
1 x 1 m to 1.2 x
2 m |
3' x 3' to 4' x
6' |
4 |
|
2 x 2 m to 2 x
10 m |
6' x 6' to 6' x
30' |
3 |
|
2 x 15 m or
larger |
6' x 50' or
larger |
2 |
Some years ago when
detectors had limited sensitivity, people began
experimenting with different loop configurations. Today
we have a variety of loop shapes in use: rectangular,
square, round, triangular and combinations of these. In
addition, agencies have tried connecting multiple loops
electrically in various series and parallel
configurations. Several things must be considered when
designing street loops for vehicle detection.
The length of the lead-in
cable will affect the overall sensitivity of the
detection area. This is a consideration only for
extremely long lead-in cables from 150 to 300 m (500 to
1000 ft) or more. If the lead-in cable of a loop is less
than 100 m (300 ft), as is the case of most
installations, then the sensitivity will not be
adversely affected. Many Diablo Controls detectors have
a range of sensitivity settings which will compensate
for even the longest lead-in lengths.
The biggest inductance
change that a detector will "see" is when the loop area
is entirely covered by a vehicle. For traffic
applications where the detection zone must cover a large
area, the vehicle detector sensitivity adjustment may
have to be increased slightly for loops which cover an
area larger than the area of the vehicle. For example,
in traffic applications, a loop which is 2 m (6 ft) feet
wide but 15 m (50 ft) long will be somewhat less
sensitive to the presence of a small motorcycle than a
smaller 1 x 1 m (4 ft by 4 ft) loop. The detector
sensitivity may have to be raised one or two levels for
the motorcycle to be adequately detected by this large
loop.
Multiple loops are often
connected to the same detector to provide a larger
detection area. This practice can lead to sensitivity
problems if the loop area is quite large. The same large
area of detection can be obtained by connecting the
loops to separate detectors or connecting a fewer number
of loops to each detector. If multiple detectors, and
multiple loops, are to be used for one detection area,
it will be necessary to parallel the relay (or solid
state) outputs together.
Many of the Diablo
Controls Inc. vehicle detectors are covered with U.S.
Patent number US 7,132,959 B2 - "Non-Interfering Vehicle
Detection". This feature minimizes the effect of
crosstalk between street loops. Cross talk is the result
of two or more loops or feeder cables affecting each
other. Detectors experiencing cross talk will usually
intermittently pick up a false "detect" or worse, drop a
"detect" when cars are indeed present. To minimize
crosstalk possibility, the street loops should be placed
as far apart as possible. A good rule is to place loops
at least 1.2 m (4 ft) apart.
Loops installed in the
vicinity of swinging or sliding gates, need special
consideration. The gate should not come closer than 1.2
m (4 ft) from the loop at any time while it is closing
or opening.
|